KTO 111 (NC), Termostatas, 0-60°C (šildytuvui)
Prekės kodas: ST.11100.0-00
Būklė: Nauja prekė
Gamintojas: STEGO
KTO 111 (NC), Termostatas, 0-60°C (šildytuvui)
11100.0-00
10 Prekės
Charakteristikos
Produkto tipas | Termostatas |
Veikimo funkcija | NC (Šildymas) |
Maitinimo įtampa | 24 V DC / 230 V AC |
Temperatūros nustatymo diapazonas | 0 ... +60 °C |
Darbinė temperatūra | -45°C ... +80°C |
Apsaugos klasė | IP20 |
Patvirtinimai | VDE, UL, EAC |
Apie prekę
The mechanical thermostats KTO 111 are regulators for use up to 5,000 meters in altitude, thanks to optimized air gap and increased creep age distance. By use of Push-In terminals, the thermostat is wired tool-free. The Push-In terminals provide constant pressure on the wires to prevent them from coming loose (e.g. during transport).
KTO 111: Thermostat (NC); contact breaker for regulating heaters. The contact opens when temperature is rising.
Switch temperature difference | 7 K (±4 K tolerance) |
---|---|
Sensor element | thermostatic bimetal |
Contact type | snap-action contact |
Service life | 100,000 cycles verified |
Max. operating voltage, frequency range | AC 250 V, 50-60 Hz |
Max. inrush current | AC 16 A for 10 sec. |
Connection1 | 2 Push-In clamps rigid wire 2.5 mm² (AWG 14) stranded wire1 1.5 mm² (AWG 16) |
Mounting | clip for 35 mm DIN rail, EN 60715 |
Casing | plastic according to UL94 V-0, light grey |
Dimensions | 60 x 33 x 41 mm |
Weight | approx. 40 g |
Fitting position | variable |
Operating/Storage temperature | -45 to +80 °C (-49 to +176 °F) |
Operating/Storage humidity | max. 90 % RH (non-condensing) |
Protection type/Protection class | IP20 / II |
Overvoltage category/Altitude | II: up to 5,000 m; III: up to 2,000 m |
1 Stripped length of rigid wire: 10 to 12 mm. When connecting with wires, wire end ferrules must be used (square or trapezoid crimp). Length of wire end ferrule: 10 mm or 12 mm.
Important note: The contact system of the regulator is subjected to environmental influences, thus the contact resistance may change. This can lead to a voltage drop and/or self-heating of the contacts.
Setting range |
Art. No. Contact breaker (NC) |
Art. No. Contact maker (NO) | Switching current²/ AC 250 V | Switching capacity AC 120 V | max. DC 24-72 V | Approvals | ||
---|---|---|---|---|---|---|---|---|
0 to +60 °C | 11100.0-00 | 11101.0-00 | 10 (2) A | 15 (2) A | 30 W | VDE | UL File No. E164102 | EAC submitted |
-10 to +50 °C | 11100.0-01 | 11101.0-01 | 10 (2) A | 15 (2) A | 30 W | VDE | UL File No. E164102 | EAC submitted |
+20 to +80 °C | 11100.0-02 | 11101.0-02 | 3 (2) A | 3 (2) A | 30 W | VDE | UL File No. E164102 | EAC submitted |
+32 to +140 °F | 11100.9-00 | 11101.9-00 | 10 (2) A | 15 (2) A | 30 W | VDE | UL File No. E164102 | EAC submitted |
+14 to +122 °F | 11100.9-01 | 11101.9-01 | 10 (2) A | 15 (2) A | 30 W | VDE | UL File No. E164102 | EAC submitted |
2 The level of switching current has an influence on the tolerance accuracy;