FZK011 (CO), Termostatas, 5-60°C (Šildymas/Aušinimas) - 01170.0-00

Prekės kodas: ST.01170.0-00

Būklė: Nauja prekė

Gamintojas:

FZK 011 | Mechaninis termostatas | Change-over Contact (Šildymas/Aušinimas)

01170.0-00

1 Vienetas

22,26 € be PVM

Charakteristikos

Produkto tipas Termostatas
Veikimo funkcija Change-over Contact (Šildymas/Aušinimas)
Maitinimo įtampa 230V AC
Temperatūros nustatymo diapazonas +5 ... +60 °C
Maksimali pradinė srovė AC 16 A for 10 sec
Darbinė temperatūra -45°C ... +65°C
Apsaugos klasė IP20
Patvirtinimai UL, EAC

Apie prekę

  • Adjustable temperature
  • High switching capacity
  • Small hysteresis
  • Change-over contact
  • Clip fixing

The mechanical thermostat is used for controlling heating and cooling equipment, filter fans or signal devices. The thermostat registers the surrounding air and can switch both inductive and resistive loads via snap-action contact. Functionality: The temperature setting on the scale equals to the upper switch point, which means that the NC contact opens. The temperature setting minus switch temperature difference (and tolerances) equals to the lower switch point, which means that the NC contact closes.

Switch temperature difference 5K (-3/+2K tolerance)¹
Sensor element thermostatic bimetal
Contact type change-over snap-action contact
Service life > 100,000 cycles
Min. switching capacity 10mA
Max. switching capacity, NC 250VAC / 120VAC, 10 (4) A
DC 30W
Max. switching capacity, NO 250VAC / 120VAC, 5 (2) A
DC 30W
Max. inrush current AC 16A for 10 sec.
Connection 4-pole terminal, clamping torque 0.5Nm max.:
rigid/stranded² wire 2.5mm² (AWG 14)
Mounting clip for 35mm DIN rail, EN 60715
Casing plastic according to UL94 V-0, light grey
Dimensions 67 x 50 x 38mm
Weight approx. 0.1kg
Fitting position variable
Operating/Storage temperature -45 to +65°C (-49 to +149°F)
Operating/Storage humidity max. 90% RH (non-condensing)
Protection type IP20
Approvals UL File No. E164102, EAC

¹ If the Normally Closed contact is used, the switch temperature difference could be reduced by connecting terminal "N" (RF heating resistor). It causes the thermal feedback which is subject to surrounding conditions and thus has to be determined for each individual application.

² When connecting with stranded wires, wire end ferrules must be used.

Important note: The contact system of the regulator is subjected to environmental influences, thus the contact resistance may change. This can lead to a voltage drop and/or self-heating of the contacts.

Art. No.Operating voltageSetting range
01170.0-00 230VAC +5 to +60°C