KFD2-SR2-EX2.W Stiprintuvas

Prekės kodas: PF.203355

Būklė: Nauja prekė

Gamintojas:

Switch Amplifier KFD2-SR2-EX2.W.

- 2-channel isolated barrier;
- 24 VDC supply (Power Rail);
- Dry contact or NAMUR inputs;
- Relay contact output;
- Line fault detection (LFD);
- Reversible mode of operation;
- Up to SIL 2 acc. to IEC 61508/IEC 61511.

Pepperl+Fuchs KFD2-SR2-EX2.W.

Kodas: 203355.

13 Prekės

173,00 € be PVM

Charakteristikos

Produkto tipas Stiprintuvas

Apie prekę

This isolated barrier is used for intrinsic safety applications.
The device transfers digital signals from NAMUR sensors or dry contacts from the hazardous area to the non-hazardous area.
The proximity sensor or the mechanical contact controls the control side load for a relay contact output. The device output changes the state when the input signal changes the state.
Via switches, the mode of operation can be reversed, and the line fault detection can be switched off.
During a fault condition, the relay reverts to its de-energized state and the LEDs indicate the fault according to NAMUR NE 44.
If the device is operated via Power Rail, additionally, a collective error message is available.

General specifications
Signal type Digital Input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Systematic capability (SC) SC 3
Supply
Connection Power Rail or terminals 14+, 15-
Rated voltage 19 ... 30 V DC
Ripple ≤ 10 %
Rated current ≤ 50 mA
Power dissipation ≤ 1 W
Power consumption ≤ 1 W
Input
Connection side field side
Connection terminals 1+, 2+, 3-; 4+, 5+, 6-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I ≤ 0.1 mA , short-circuit I > 6 mA
Pulse/Pause ratio min. 20 ms / min. 20 ms
Output
Connection side control side
Connection output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Output I, II signal, relay
Contact loading 250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 40 V DC/2 A resistive load
Minimum switch current 2 mA / 24 V DC
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Mechanical life 107 switching cycles
Collective error message Power Rail
Transfer characteristics
Switching frequency ≤ 10 Hz
Galvanic isolation
Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elements LEDs
Control elements DIP switch
Configuration via DIP switches
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EU EN 61010-1:2010+A1:2019+A1:2019/AC:2019
Conformity
Electromagnetic compatibility NE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018
Degree of protection IEC 60529:1989+A1:1999+A2:2013
Functional safety IEC/EN 61508:2010
Input EN 60947-5-6:2000
Ambient conditions
Ambient temperature -20 ... 70 °C (-4 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 150 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate PTB 00 ATEX 2080
Marking Ex-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Input Ex ia
Voltage 10.5 V
Current 13 mA
Power 34 mW (linear characteristic)
Supply
Maximum safe voltage 253 V AC / 125 V DC (Attention! Um is no rated voltage.)
Output
Maximum safe voltage 253 V AC (Attention! The rated voltage can be lower.)
Fault indication output
Maximum safe voltage 40 V DC (Attention! Um is no rated voltage.)
Certificate PF 08 CERT 0803
Marking Ex-Hexagon II (3)G [Ex ic Gc] IIC
Input Ex ic
Voltage 10.5 V
Current 13 mA
Power 34 mW (linear characteristic)
Certificate TÜV 99 ATEX 1493 X
Marking Ex-Hexagon II 3G Ex ec nC IIC T4 Gc
Galvanic isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019
International approvals
FM approval
FM certificate FM19US0207X
Control drawing 116-0035
UL approval E106378
Control drawing 116-0473 (cULus)
Contact loading 250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 30 V DC/2 A resistive load
IECEx approval
IECEx certificate IECEx PTB 11.0034 , IECEx TUN 19.0013X
IECEx marking [Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I
Ex ec nC IIC T4 Gc
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Atsisiųsti

GAUKITE NAUJIENAS!

Prisijunkite nemokamai dabar ir pirmieji gaukite naujienas, informaciją apie nuolaidas ir specialius pasiūlymus.